Loading...
HomeMy WebLinkAboutZion Community Hall Community Services Committee AREA CODE 416 HEADQUARTERS AND OFFICE_ TELEPHOmE 623-r,126 132 CHURCH SIRErT ROWMANVWLE, ONTARIO FIRE DEPARTMENT CORPORA110N OF THE TOWN OF NEWCASTLE INFORMATION TO: Councillor Donald Allin, Chairmant Community Services Committee FROM: J. Hayman, Area Fire Chief SUBJECT: Zion Community Hall DATE: July 189 1975, Subsequent to an inspection of the Community Building at Zion Park on Wednesday July 16, 1975, with building inspector H.p Wight. There has been no alterations to the building since the inspection of February 2, 1975. The following are the necessary fire safety requirements* 1. Install a landing and stairs from the north-west emergency exit. 2. Panic-bar hardware to be installed on exit doors. 3. Illuminated exit lights for all exits. 4. Furnace room to have a 1. hr. fire separation,, with combustible air and ventilation from the exterior. (would recommend to be relocated to the basement, with a pre-fab factory built chimney). 5. Kitchen requires a 3/4 hr. fire separation, with vapour removal exhaust system for cooking appliances. 6. Necessary portable fire extinguishers.